Issue:
"PLC reservation failed" error message when upgrade the firmware of my PLC using the EcoStruxure Automation Device Maintenance tool
Product Line:
EcoStruxure Automation Device Maintenance
Resolution:
The error is generated when there is an existing programming connection to the PLC and you try to connect to the PLC using the EcoStruxure Automation Device Maintenance tool. to clear the error, disconnect from the PLC with Control Expert/Unity Pro

"PLC reservation failed" error message when upgrade the firmware of my PLC using the EcoStruxure Automation Device Maintenance tool
Product Line:
EcoStruxure Automation Device Maintenance
Resolution:
The error is generated when there is an existing programming connection to the PLC and you try to connect to the PLC using the EcoStruxure Automation Device Maintenance tool. to clear the error, disconnect from the PLC with Control Expert/Unity Pro
Released for:Schneider Electric Global

