Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric corporate Website

		
Search FAQs
What are the Ground Fault Alarm pickup, dropout and time delay settings for Micrologic P and H trip units?
Issue:  Ground Fault alarm settings for Micrologic 5.0P, 6.0P, 5.0H, 6.0H trip units
Product Line: Circuit Breakers
Environment: Masterpact NW and NT, Powerpact P and R, Compact NS

Resolution:
100-400 amp sensors have a pickup and dropout range of .3xIn - 1xIn with a 1-10 second time delay
600-1200 amp sensors have a pickup and dropout range of .2xIn - 1xIn with a 1-10 second time delay
1250-6300 amp sensors have a pickup and dropout range of .1xIn - 1200 amps with a 1-10 second time delay

1 amp increments
0.1 second increments

Schneider Electric Global

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Our Mission
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Financial Results
  • Annual Reports
  • Share Price
  • Investor Events
  • Careers
  • Sustainability
  • Electricity 4.0
  • Next-generation Automation
  • AI and Technology
  • Reports
  • Foundation
  • Consulting
  • Global - FR
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Change your cookie settings