The timer resets on a power cycle because the customer has made a Project Backup. When a Project backup is made, every power cycle
will cause a cold restart (%S0). This cold restart will reset all timers.
Released for:Schneider Electric Global






{}
The timer resets on a power cycle because the customer has made a Project Backup. When a Project backup is made, every power cycle
will cause a cold restart (%S0). This cold restart will reset all timers.