Issue:
Cooling fans run adjustments on ATV630 and ATV930 Process Drives
Product Line:
Altivar ATV630 and ATV930
Environment:
All
Cause:
Wants to know when the fans run on the drive.
Resolution:
The fans for the drive up to 90kW can be run in 3 modes :
- Standard : at run order
- Always : the fans run permanently
- Economy : The fans run according to the drive thermal state
For the drives upper than 90kW, the fans run only at run order.
Cooling fans run adjustments on ATV630 and ATV930 Process Drives
Product Line:
Altivar ATV630 and ATV930
Environment:
All
Cause:
Wants to know when the fans run on the drive.
Resolution:
The fans for the drive up to 90kW can be run in 3 modes :
- Standard : at run order
- Always : the fans run permanently
- Economy : The fans run according to the drive thermal state
For the drives upper than 90kW, the fans run only at run order.
Released for:Schneider Electric Global

