All TesysT registers accessible by custom logic have the same addresses.
In general, TesysT registers have the same addresses expect the canopen, devicenet or ethernet IP because of different type of addressing (e.g. index/subindex or assembly instead of logic address)
When comparing ModbusTCP with Modbus RTU, there is very little difference.
There are few register with faster refresh data allocated for MOdbusTCP because MOdbusTCP is faster as ModbusRTU. These registers are 2500 – 2507.
Nevertheless, registers 2500-2507 just mirror other registers and so ModbusTCP can use standard registers or mirror registers.
Here is the simple summary of difference:
Read only registers (read by PLC) :
Modbus RTU ---- Modbus TCP
Status 1 register 455 455 or 2502
Status 2 register 456 456 or 2503
Logic inputs status 457 457 or 2504
Logic outputs status 458 458 or 2505
Read/write registers (written by PLC) :
Modbus RTU ---- Modbus TCP
Control register 704 704 or 2507
Additionally there might be other few registers related to services available only on Modbus TCP/ethernet, e.g. SNMP, RSTP, IP address, mask.
In general, TesysT registers have the same addresses expect the canopen, devicenet or ethernet IP because of different type of addressing (e.g. index/subindex or assembly instead of logic address)
When comparing ModbusTCP with Modbus RTU, there is very little difference.
There are few register with faster refresh data allocated for MOdbusTCP because MOdbusTCP is faster as ModbusRTU. These registers are 2500 – 2507.
Nevertheless, registers 2500-2507 just mirror other registers and so ModbusTCP can use standard registers or mirror registers.
Here is the simple summary of difference:
Read only registers (read by PLC) :
Modbus RTU ---- Modbus TCP
Status 1 register 455 455 or 2502
Status 2 register 456 456 or 2503
Logic inputs status 457 457 or 2504
Logic outputs status 458 458 or 2505
Read/write registers (written by PLC) :
Modbus RTU ---- Modbus TCP
Control register 704 704 or 2507
Additionally there might be other few registers related to services available only on Modbus TCP/ethernet, e.g. SNMP, RSTP, IP address, mask.
Released for:Schneider Electric Global