Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric corporate Website

Search FAQs
ATV6xx, ATV9xx when monitoring LCr (motor current) over communications, what feedback would you expect?

Article available in these languages: Spanish

Issue:
Expected feedback while monitoring LCr (motor current) over Communications.

Product Line:
ATV

Environment:
All

Cause:
Communication

Resolution:
LCR unit: [A]
drives up to     ..D15           coeff.: 0.01
drives:     D18..  to ..C16     coeff.: 0.1
drives higher than     C16..  coeff.: 1

Schneider Electric Global

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: