{}

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric corporate Website

Search FAQs
For Modbus Serial communication between M241/M251/M262 and Altivar 320 Polarization Resistor?
Issue
For Modbus Serial communication between M241/M251/M262 and Altivar 320, does the Polarization Resistor setting need to be turned on?

Product Line
Altivar 320, Modicon M241, Modicon M251, Modicon M262, EcoStruxure Machine Expert / SoMachine

Environment
Serial Communication setup in PLC configuration software

Resolution
Yes, polarization must be turned on in the PLC as per p27 of the ATV320 Modbus Manual:
(Document Reference#NVE41308)
https://www.se.com/ww/en/download/document/NVE41308/

To apply the setting, in EcoStruxure Machine Expert (or the previous version SoMachine):
  1. In the Devices Tree of your EcoStruxure Machine Expert / SoMachine project, expand the tree for your PLC.
  2. Doubleclick on the Serial_Line_1 (or Serial_Line_2)node
  3. Under "Physical Medium", choose "Yes" in the dropdown list for Polarization Resistor

Schneider Electric Global

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: