{}

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric corporate Website

Search FAQs
How can I reset fault using the STOP/RESET key of Graphic Display Terminal on the Altivar Process Drive?

Article available in these languages: Japanese

Issue:
Is there a way to use the STOP/RESET key on the Graphic Display Terminal to reset Fault on the Altivar Process Drive?

Product Line:
Altivar Process Drive ATV630 ATV930

Environment:
All

Cause:
Customer would like to reset fault using the STOP/RESET key on the Graphic Display Terminal.

Resolution:
In order to press the STOP/RESET key on the Graphic Display Terminal to perform fault reset, active command channel is set to HMI.
Or:
Go to complete setting, then command reference, and scroll down to HMI cmd and set it to bumpless.
Toggle the LOCAL/REMOTE key to go to HMI, then press STOP/RESET to perform Fault Reset.

Schneider Electric Global

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: